Chimney inspections

  • Home Chimney inspections

Inspection and cleaning of chimneys (flues), revisions and approvals of chimneys, Professional examination of chimneys, Measurement of flue gases, Consultancy

We offer our services only to corporate clients

Decree No. 401/2007 Coll. of the Ministry of the Interior of the Slovak Republic imposes obligations to the operator not only in the construction but also in the operation of chimney bodies according to § 20 as follows
  • The chimney must be maintained in good technical condition and must be secured its regular inspection and cleaning
  • The chimney must be cleaned and inspected at least at the following times during operation periods:
    • if appliances with a total heat output of up to 50 kW are connected to the chimney body, once per:
      • four months if appliances are connected to the chimney for solid fuel or liquid fuel appliances
      • six months if appliances are connected to the chimney for gaseous fuels and if the chimney is unlined
      • twelve months if appliances are connected to the chimney gaseous fuel appliances and if the chimney is lined
    • if appliances with a total heat output of more than 50 kW are connected to the chimney body, once per:
      • two months if appliances are connected to the chimney for solid fuel or liquid fuel appliances
      • six months if appliances are connected to the chimney for gaseous fuels
  • The chimney to which a Type C gas-fired appliance is connected shall be be inspected and cleaned at least once a year during operation
  • A chimney to which a solid fuel appliance, a liquid fuel appliance or a gas fuel appliance is connected and which has not been in operation since the other cleaning and inspection for longer than the period established in paragraph 2 letter a) and b), it does not have to be checked and cleaned until it is put back into operation; before putting the appliance into operation, it must be checked and cleaned.
  • The chimney in occasionally used buildings must be cleaned and inspected at least once every two years
  • Soot and condensate accumulated in the collection part of the chimney vent must be removed every time the chimney is cleaned
  • The appliance must be cleaned within the time limits specified by its manufacturer in in the documentation accompanying the appliance. If this period is not specified in the documentation or such documentation is missing, it must be cleaned within the time limits specified in paragraph 2